Primary Current

Transformers

Designation according to IEC 60044 part 2:

825-CBCT Core Balance

Current Transformer

Minimum Nominal Operating Voltage

Nominal Operating Voltage of Motor

Minimum Rated Primary Current l

1n

Nominal Operating Current of Motor

Rated Secondary Current [A]

825-MCM2

825-MCM5

825-MCM20

1

25

5

Class and Nominal Overcurrent Protection

5P10 ext. 120% ➊

Power Rating

According to power consumption in leads and measuring circuit.

Rated Frequency

50/60 Hz

Burden

825-MCM2

825-MCM5

825-MCM20

Power Consumption at Maximum Rated Current
[VA/phase]

0.1

0.2

0.4

Continuous Thermal Current [A]

3

6

24

Thermal Current, 1 s Duration [A]

250

400

600

No Load

An open-circuit secondary is permitted, as the burden is provided
in the converter module circuitry.

5

Total Measurement Error (percentage):

± 5% within range up to rated nominal overcurrent
± 1% at rated nominal primary current

P

For Protection Purposes

10

Rated Nominal Overcurrent Factor:

10X rated nominal primary current

ext.

120%

Extended Rated Thermal Current:

120% of rated nominal primary current (if l

e

motor > 87%

of rated nominal transformer current)

Ratio

100:1

Current Range

0.5...10 A

Continuous Thermal Current

0.5 A

Saturation Current

30 A

Thermal Current, 1 s Duration

25 A

Rated Burden at Maximum Rated Current

0.4 V A

Rated Frequency

50/60 Hz