The relay asserts the Emergency Restart bit in response to any of the following
conditions:

the control input assigned to Emergency Restart asserts.

the relay receives a network Emergency Restart control command.

When the Emergency Restart bit asserts, the relay does the following:

Resets the motor thermal element capacity used to 0%.

Manipulates the Starts-Per-Hour, Minimum Time Between Starts, and
Anti-backspin functions to permit an immediate start.

De-asserts the Trip output contact if a fault detecting element is not

picked up.

Initiates a motor start.