Parameter List Chapter B
RTD
Settings
(cont.)
186
40087
400087
RTD2 LOCATION
0 = Off
1 = Wdg
2 = Brg
3 = Amb
4 = Oth
0
—
—
Get/Set
187
40088
400088
RTD2 TYPE
0 = Pt100
0
—
—
Get/Set
188
40089
400089
RTD2 TRIP LEVEL
0 = Off
250
0
1
°C
Get/Set
189
40090
400090
RTD2 WARN LEVEL
0 = Off
250
0
1
°C
Get/Set
190
40091
400091
RTD3 LOCATION
0 = Off
1 = Wdg
2 = Brg
3 = Amb
0
—
—
Get/Set
191
40092
400092
RTD3 TYPE
0 = Pt100
0
—
—
Get/Set
192
40093
400093
RTD3 TRIP LEVEL
0 = Off
250
0
1
°C
Get/Set
193
40094
400094
RTD3 WARN LEVEL
0 = Off
250
0
1
°C
Get/Set
194
40095
400095
RTD4 LOCATION
0 = Off
1 = Wdg
2 = Brg
3 = Amb
4 = Oth
0
—
—
Get/Set
195
40096
400096
RTD4 TYPE
0 = Pt100
1 = Ni100
2 = Ni120
3 = Cu10
0
—
—
Get/Set
196
40097
400097
RTD4 TRIP LEVEL
0 = Off
250
0
1
°C
Get/Set
197
40098
400098
RTD4 WARN LEVEL
0 = Off
250
0
1
°C
Get/Set
198
40099
400099
RTD5 LOCATION
0 = Off
0
—
—
Get/Set
199
40100
400100
RTD5 TYPE
0 = Pt100
0
—
—
Get/Set
200
40101
400101
RTD5 TRIP LEVEL
0 = Off
250
0
1
°C
Get/Set
201
40102
400102
RTD5 WARN LEVEL
0 = Off
250
0
1
°C
Get/Set
202
40103
400103
RTD6 LOCATION
0 = Off
1 = Wdg
2 = Brg
3 = Amb
4 = Oth
0
—
—
Get/Set
203
40104
400104
RTD6 TYPE
0 = Pt100
1 = Ni100
2 = Ni120
3 = Cu10
0
—
—
Get/Set
204
40105
400105
RTD6 TRIP LEVEL
0 = Off
250
0
1
°C
Get/Set
205
40106
400106
RTD6 WARN LEVEL
0 = Off
250
0
1
°C
Get/Set
206
40107
400107
RTD7 LOCATION
0 = Off
1 = Wdg
2 = Brg
3 = Amb
0
—
—
Get/Set
Group
DeviceNet
Param No.
Modbus Register
Parameter Name
Min
Max
Default
Scale
Factor
Units
Access
Read (0x03h)
Write (0x06h)