The thermal meter function also reports the state of connected RTDs if any have
failed. Table 48 shows failure messages.

Power Measurement
Conventions

The 825-P uses the IEEE convention for power measurement assuming motor
action. The implications of this convention are shown in Figure 35.

Figure 35 - Complex Power Measurement Conventions

In the 825-P, reported positive real power is always into the motor.

Table 48 - RTD Input Status Messages

Message

Status

Open

RTD leads open

Short

RTD leads shorted

Comm Fail

Fiber-optic communications to 825-PR12D Module have failed

Stat Fail

825-PR12D Module self-test status failure

Power Into Motor

Q+ (VAR)

I leads V

W = –

VAR = –

PF = LAG

I lags V

W = –

VAR = +

PF = LEAD

P+ (W)

I leads V
W = +
VAR = –
PF = LEAD

I lags V
W = +
VAR = +
PF = LAG

M

825-P

Relay

Source

Bus

Direction of
Positive Real Power

Motor