Features – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual
Page 115
Rockwell Automation Publication 825-UM004D-EN-P - November 2012
115
825-PDN DeviceNet Communication Card Chapter 9
Features
The 825-P DeviceNet Communication Card features the following:
•
The card receives the required power from the DeviceNet network.
•
Rotary switches let you set the node address and network data rate prior to
mounting in the 825-P Modular Protection System and applying power.
Alternatively, the switches can be set to positions that allow for
configuration of these settings over the DeviceNet network, utilizing a
network configuration tool such as RSNetWorx for DeviceNet.
•
Status indicators report the status of the device bus and network
communications. They are visible from the back panel of the 825-P
Modular Protection System as installed.
•
UCMM (Unconnected Message Manager) messages are supported with
the ability to allocate up to 3 explicit message connections concurrently.
•
DeviceNet Group 2 slave functionality including:
–
Explicit connection
–
Polled connection
–
1 COS (Change of State)/Cyclic connection
•
Full DeviceNet Parameter Object support allows EDS files to be extracted
from all units.
•
Settings are provided for user-defined behavior of the 825-P Modular
Protection System auxiliary relays for Comm Fault and Comm Idle
conditions.
•
Group 4 faulted node recovery is supported. You can configure a device
even when it is faulted on the network if the configuration tool supports
faulted node recovery.
•
DeviceLogix component technology provides the capability to perform
logic operations at the device level. A total of 80 function blocks are
supported.