Front Panel Operation

Front Panel Layout

The 825-P Relay front-panel interface consists of two LEDs, an LCD display,

a seven-button keypad, and an EIA-232 serial port connector. The front-panel
layout is shown in Figure 22.

Figure 22 - Relay Front Panel

Normal Front Panel Display

In normal operation, the relay ENABLE LED is illuminated and the LCD
display screen is on. The LCD screen rotates displays showing each screen for
about two seconds before moving to the next. The default rotating display screens
include Unit ID Line 1, Unit ID Line 2, line currents, and voltages (if available).
Enable the relay to add display messages as noted in the Display Enable settings

in Table 41.

Figure 23 - Default Display Screen

Use the UNIT ID LINE 1 (RID) and UNIT ID LINE 2 (TID) settings
described in Identifier Settings to change the contents of the information shown
in Figure 23.

If the front panel was in Access Level 2, it automatically returns to the default
display when the display times out. For more information, see Table 40.

LCD Display

Displays real-time and historic

information as well as relay setting

menus.

Arrows

Navigates through
menus or data lists
shown in the LCD Display.

Enter

Allows movement from
the default display to
the main menu.

Test/Reset

When pushed, will trip-test the relay

OR resets the trip.

Trip LED

Flashes to indicate alarm conditions

and illuminates solid to inidcate trip.

Enable LED

Illuminates when relay is operational.

EIA-232 Serial Port

Allows quick access to all relay data,

control, and setting functions using

a PC, serial cable, and software.

Escape

Reactivates the LCD Display

back-lighting and backs out of the

current menu or display.

PORT F

ENABLE

TRIP

TEST/RESET

ESC

825-P Modular

Prot. System