beautypg.com

Required equipment, Equipment shipping with the card, User-supplied equipment – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual

Page 116: Wiring, Use static control precautions, Connect a devicenet cable to the network

background image

116

Rockwell Automation Publication 825-UM004D-EN-P - November 2012

Chapter 9 825-PDN DeviceNet Communication Card

Required Equipment

Equipment Shipping with the Card

When you unpack the card, verify that the package includes:

One DeviceNet communication card

One five-pin linear DeviceNet plug

Two labels that the installer affixes to the 825-P Modular Protection
System, one to the top and one to the back panel

825-P Option Card installation instructions

User-Supplied Equipment

Small slotted screwdriver (0.6 x 3.5 mm)

DeviceNet cable, a thin cable with outside diameter of 6.9 mm (0.27 in.),

is recommended

Configuration tool (e.g., RSNetWorx for DeviceNet)

Computer with an installed DeviceNet communication adapter

825-P User Manual

Wiring

1.

Remove power from the DeviceNet network and 825-P Modular
Protection System relay

2.

Use static control precautions

3.

Connect a DeviceNet cable to the network

4.

Terminate the bare leads of the DeviceNet cable to the 5-pin linear plug

as illustrated in Figure 40