62h Read Enumeration

Text Command

The 825-P uses this function to allow a Modbus master to read parameter
enumeration or bit enumeration values (setting lists) from the relay. One
parameter enumeration is read in each query.

Table 80 - 62h Read Enumeration Text Command

The relay responses to errors in the query are shown below:

Table 81 - 61h Read Parameter Enumeration Text Query Error Messages

Bytes

Field

Requests from the master must have the following format:

1 byte

Slave Address

1 byte

Function Code (62h)

2 bytes

Parameter Number

1 byte

Enumeration Index

2 bytes

CRC-16

A successful response from the slave will have the following format:

1 byte

Slave Address

1 byte

Function Code (62h)

2 bytes

Parameter Number

1 byte

Enumeration Index

16 bytes

Enumeration Text

2 bytes

CRC-16

Error

Error Code Returned

Communication

Counter Increments

Illegal parameter to read

Illegal Data Value (03h)

Illegal Register