beautypg.com

Table 58 - message configuration – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual

Page 123

background image

Rockwell Automation Publication 825-UM004D-EN-P - November 2012

123

825-PDN DeviceNet Communication Card Chapter 9

CT Ratio. See Table 59, Common Configuration Examples for 825-P Modular
Protection System for additional configurations.

Table 58 - Message Configuration

Table 59 - Description of Message Configuration Fields

Field

Description

Message Type

Select CIP Generic from pull-down menu to configure an explicit message.

Destination

Element

Tag name of the location you are going to place the response information. In this example
a tag was created with the name explicit_data.

Service Type

Pull-down menu has several options, however only the Get Attribute Single is used for this
example. The Class, Instance, and Attribute define the actual information being requested.
Additional configurations of these parameters can be found in Appendix B.

Class

In this example, the value is F.

Instance

In this example, the value is 104.

Attribute

In this example, the value is 1.

After the above information has been entered, click on the communication tab

Path

Path defines the route the message takes to get to the device it is intended for. In this
example the path is Scanner,2,4; where scanner is the name of the 1756-DNB in the rack,
2 represents the DeviceNet port, and 4 represents the physical node address of the 825-P
Modular Protection System.