Chapter E DeviceNet Information
Instance 2 is the Predefined Group 2 Connection Set Polled IO Message
Connection. The following Instance 2 attributes are supported:
14
Get
Produced Connection Path
Empty
15
Get
Consumed Connection Path Length
UINT
0
16
Get
Consumed Connection Path
Empty
Attribute ID
Access Rule
Name
Data Type
Value
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
State
USINT
0 = nonexistant
1 = configuring
3 = established
4 = timed out
2
Get
Instance Type
USINT
1 = I/O Connection
3
Get
Transport Class Trigger
USINT
0x82 - Server, Transport Class 2
(If alloc_choice ! = polled and
ack suppression is enabled then
value = 0x80)
4
Get
Produced Connection ID
UINT
01111xxxxxx
xxxxxx = node address
5
Get
Consumed Connection ID
UINT
10xxxxxx101
xxxxxx = node address
6
Get
Initial Comm Characteristics
USINT
0x21
7
Get
Produced Connection Size
UINT
0 to 8
8
Get
Consumed Connection Size
UINT
0 to 8
9
Get/Set
Expected Packet Rate
UINT
in milliseconds
12
Get/Set
Watchdog Action
USINT
0 = transition to timed out
1 = auto delete
2 = auto reset
13
Get
Produced Connection Path Length
UINT
8
14
Get/Set
Produced Connection Path
21 04 00 25 (assy inst #) 00 30
03
15
Get
Consumed Connection Path Length
UINT
8
16
Get/Set
Consumed Connection Path
21 04 00 25 (assy inst #) 00 30
03