Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual

Page 236

background image

236

Rockwell Automation Publication 825-UM004D-EN-P - April 2012

Chapter C Relay Word Bits

1

49T

7

Thermal (Overload) Trip. Assert when the relay issues a thermal element trip because of locked rotor starting or running overload conditions.

LOSSTRIP

6

Load-Loss Trip. Assert when the relay detects a load-loss as defined by that function and its settings.

JAMTRIP

5

Load-Jam Trip.

46UBT

4

Phase Current Unbalance Trip. Assert when the relay issues a trip in response to a current unbalance condition, as defined by that function and
its settings.

50P1T

3

Definite-Time Phase Overcurrent (Short Circuit Trip Level.

RTDT

2

Winding and Bearing RTD Overtemperature Trip.

PTCTRIP

1

Asserts when measured PTC loop resistance is greater than trip value.

50G1T

0

Definite-Time Residual Overcurrent (Trip Level.

2

VART

7

Reactive Power Trip. Assert when the relay issues a reactive power element trip.

37PT

6

Underpower Trip. Assert when the relay issues an underpower element trip.

27P1T

5

Phase Undervoltage Trip Definite time delayed.

59P1T

4

Phase Overvoltage Trip Definite time delayed).

47T

3

Phase Reversal Trip. Asserts when the relay detects a phase reversal condition.

55T

2

Power Factor Trip. Assert when the relay issues a power factor element alarm or trip.

SPDSTR

1

Speed Switch Trip. Asserts when the relay does not detect a speed switch contact closure within a settable trip period from the beginning of a
motor start.

50N1T

0

Definite-Time Neutral (Core Balance) Overcurrent.

3

SMTRIP

7

Asserts when Start Motor Timer times out.

81D1T

6

Definite-Time Over- and Underfrequency Element (Trip Level 1). Assert when the frequency has been either above or below the element set
point for a definite time.

81D2T

5

Definite-Time Over- and Underfrequency Element (Trip Level 2). Assert when the frequency has been either above or below the element set
point for a definite time.

OTHTRIP

4

Other Temperature Trip. Asserts when one or more healthy Other RTD temperature exceeds the trip set points.

AMBTRIP

3

Ambient Temperature Trip. Asserts when the healthy ambient RTD temperature exceeds its trip set point.

PTCFLT

2

Indicates faulted/shorted thermistor.

RTDFLT

1

Asserts when an open or short circuit condition is detected on any enabled RTD input, or communication with the external RTD module has
been interrupted.

MCMFLT

0

Asserts when the MCM module detected does not agree with the relay part number.

4

COMMIDLE

7

DeviceNet Card in programming mode.

COMMLOSS

6

DeviceNet communication fail.

REMTRIP

5

Remote Trip Control Input Asserted.

COMMFLT

4

Internal communication time-out.

*

3

Reserved for future use.

*

2

Reserved for future use.

*

1

Reserved for future use.

*

0

Reserved for future use.

5

49A

7

Thermal (Overload) Alarm. Assert when the relay issues a thermal element alarm/warning because of locked rotor starting or running
overload conditions.

LOSSALRM

6

Load-Loss Alarm/Warning. Assert when the relay detects a load-loss as defined by that function and its settings.

JAMALRM

5

Load-Jam Alarm/Warning.

Table 112 - Relay Word Bit Definitions for the 825-P (Sheet 2 of 4)

Row #

Bit

Definition