beautypg.com

Fuse replacement, De-energize the relay, Remove the slot a printed circuit board – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual

Page 32: Locate the fuse on the board, Remove the fuse from the fuse holder, Insert the printed circuit board into slot a, Real-time clock battery replacement, Remove the slot b printed circuit board, Locate the battery clip (holder) on the board, Remove the battery from beneath the clip

background image

32

Rockwell Automation Publication 825-UM004D-EN-P - November 2012

Chapter 2 Installation

Fuse Replacement

To replace the Power Supply fuse, do the following:

1.

De-energize the relay.

2.

Remove the eight rear-panel screws, the ground screw, and the relay rear-
panel.

3.

Remove the Slot A printed circuit board.

4.

Locate the fuse on the board.

5.

Remove the fuse from the fuse holder.

6.

Replace the fuse with a BUSS 2A/250V ABC (ceramic) or equivalent.

7.

Insert the printed circuit board into Slot A.

8.

Reinstall the relay rear-panel and ground screw, and then energize the relay.

Real-Time Clock Battery Replacement

To replace the real-time clock battery, do the following:

1.

De-energize the relay.

2.

Remove the eight rear-panel screws, the ground screw, and the

relay rear-panel.

3.

Remove the Slot B printed circuit board.

4.

Locate the battery clip (holder) on the board.

5.

Remove the battery from beneath the clip.

6.

Properly dispose of the old battery.

7.

Install the new battery with the positive (+) side facing up.

8.

Insert the printed circuit board into Slot B.

9.

Reinstall the relay rear-panel and ground screw, and then energize the relay.

10.

Set the relay date and time.