Power and power factor measuring accuracy, Wye-connected voltages, Figure 51 - wye voltage source connections – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual

Page 153

background image

Rockwell Automation Publication 825-UM004D-EN-P - November 2012

153

Testing & Troubleshooting Chapter 11

Power and Power Factor Measuring Accuracy

The following tests assume use of an MCM2, MCM5, or MCM20 converter
module.

Wye-Connected Voltages

Perform the following steps to test wye-connected voltages:

1.

Connect the current source to the MCM module, as shown in Figure 50.

2.

Connect the voltage source to the 825-P, as shown in Figure 51. Make sure
that Xfmt Connection = Wye.

Figure 51 - Wye Voltage Source Connections

3.

Using the front panel SET/SHOW or MPS Explorer software, record the
Phase CT Ratio, Phase VT Ratio, and Phase Rotation setting values.

4.

Apply the current and voltage quantities shown in Column 1 of Table 87.

Values are given for Phase Rotation = ABC and Phase Rotation = ACB.

5.

Use the front panel METER function or MPS Explorer software to verify
the results.

|IA| = FLA

12%

|IB| = 1.2 • FLA
|IC| = 1.2 • FLA
|IA| = 0.9 • FLA

13%

|IB| = 1.1 • FLA
|IC| = 1.1 • FLA

Table 86 - Current Unbalance Measuring Accuracy

|I| Applied (A secondary)

Expected Reading (%)

Actual Reading (%)

825-P

L1

L2

L3

N

Voltage

Test

Source

VA

VB

VC

VN