49

Hardware Commissioning Chapter 4

Adding the Optional
Communication Card

Remove control power from the relay, and remove the back cover

Add the optional communication card into Slot C in the 825-P

Replace the cover and reapply control power to the relay

Navigate to Main > Status to view the Status display

If the display shows the following message:

Press the Enter key to confirm that you want this hardware change

Select Yes to confirm the new hardware configuration, and the display

will show:

Press Enter to reboot the relay

If there is an address conflict on the internal communication bus, the
display show the following message:

To correct this conflict, navigate to Main > Set/Show > Port > Port 4

and select the parameter named “Modbus Slave ID”

Change the Modbus Slave ID to the value of 247

Press the ESC key, and the display will show the following message:

Select Yes to resolve the address conflict

Confirm Hardware

Config (Enter)

Confirm Config?

Yes No

Config Accepted

Enter to Reboot

COMMFLT

Warning

Save Changes?

Yes No