Rockwell Automation Publication 825-UM004D-EN-P - November 2012

151

Testing & Troubleshooting Chapter 11

20.

Perform any protection element tests using the individual element test
procedures in Selected Functional Tests on page 151.

Perform the tests until it is proven that the relay operates as intended.
Exhaustive element performance testing is not necessary for
commissioning.

21.

Connect the relay for tripping duty.

22.

Verify that any settings changed during the tests performed in Step 19 and
Step 20 are changed back to the correct values for your application.

23.

Prepare the relay for operation by clearing the relay data buffers using

MPS Explorer software.

Clearing the relay buffers prevents data generated during commissioning
testing from being confused with operational data collected later.

24.

Start the motor only when it is safe to do so.

25.

Verify the following AC quantities using the front panel METER or serial
port METER command:

phase current magnitudes are nearly equal and

phase current angles are balanced, have proper phase rotation, and have
the appropriate phase relationship to the phase voltages.

26.

If your relay is equipped with voltage inputs, verify the following:

phase voltage magnitudes are nearly equal.

Phase voltage phase angles are balanced and have proper phase rotation.

The 825-P relay in now ready for continuous service.

Selected Functional Tests

Phase Current Measuring Accuracy

1.

Connect the current source to the MCM converter module, as shown in
Figure 50.

Figure 50 - Current Source Connections

MCM

825-P

Cable with

Plugs

1

3

5

2

4

6

Current

Test

Source

IA

IB

IC

IN