beautypg.com

0x0e, 0x05, Get_attribute_single – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual

Page 244: Reset, Message router - class code 0x0002, Devicenet object - class code 0x0003, Revision, Uint, Get/set

background image

244

Rockwell Automation Publication 825-UM004D-EN-P - April 2012

Chapter E DeviceNet Information

The following common services are implemented for the Identity Object:

Message Router - CLASS

CODE 0x0002

No class or instance attributes are supported. The message router object exists
only to rout explicit messages to other objects.

DeviceNet Object - CLASS

CODE 0x0003

The following class attributes are supported for the DeviceNet Object:

Only Instance 1 of the DeviceNet Object is supported. The following instance
attributes are supported:

**

Allocation_byte Bit 0 Explicit messaging

Bit 1 Polled I/O

Bit 4 COS I/O

Bit 5 Cyclic I/O

Bit 6 Acknowledge Suppression

The following services are implemented for the DeviceNet Object:

Service Code

Implemented for:

Service Name

Class

Instance

0x0E

No

Yes

Get_Attribute_Single

0x05

No

Yes

Reset

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

Revision

UINT

2

Attribute ID

Access Rule

Name

Data Type

Value

1

Get/Set

Node Address

USINT

0-63

2

Get/Set

Baud Rate

USINT

0=125K

1=250K

2=500K

5

Get

Allocation Info

Allocation Choice
Master Node Addr

Structure of

BYTE
USINT

Allocation_byte**

0-63 = address

255 = unallocated

8

Get

MAC ID Switch Value

USINT

0-63