Configuration, Basic configurations – Lenze EVS9332xP User Manual
Page 293

Configuration
Basic configurations
8.5
l
8.5−27
EDSVS9332P EN 5.0−07/2013
IMPORTANT
Possible settings
Code
Selection
Lenze
Designation
No.
C0590 MONIT P13
0
0
2
3
TRIP
Warning
Off
P13 monitoring
Configuration of angle error
monitoring
l
The following error is
monitored by the DFSET
function block. The
monitoring is only active if
DFSET is used.
C0591 MONIT CE1
3
0
2
3
TRIP
Warning
Off
CE1 monitoring
Configuration of "CAN−IN1
fault" monitoring
C0592 MONIT CE2
3
0
2
3
TRIP
Warning
Off
CE2 monitoring
Configuration of "CAN−IN2
error" monitoring
C0593 MONIT CE3
3
0
2
3
TRIP
Warning
Off
CE3 monitoring
Configuration of "CAN−IN3
error" monitoring
C0594 MONIT SD6
®
0
2
3
TRIP
Warning
Off
SD6 monitoring
Configuration of "motor
temperature sensor"
monitoring
à
Depends on C0086
C0595 MONIT CE4
3
0
2
3
TRIP
Warning
Off
CE4 monitoring
Configuration of "CAN bus off"
monitoring
C0596 NMAX LIMIT
5500
0
{1 rpm}
16000 System speed monitoring
C0597 MONIT LP1
3
0
2
3
TRIP
Warning
Off
LP1 monitoring
Configuration of motor phase
failure monitoring
C0598 MONIT SD5
3
0
2
3
TRIP
Warning
Off
SD5 monitoring
Configuration monitoring
master current at X5/1.2 < 2mA
C0599 LIMIT LP 1
5.0
1.0
{0.1 %}
10.0 LP1 monitoring
Current limit value for motor
phase monitoring
C0600 FUNCTION
1
0
1
2
3
4
5
OUT = IN1
IN1 + IN2
IN1 − IN2
IN1 * IN2
IN1 / IN2
IN1/(100% − IN2)
ARIT2
Function selection
See system
manual
(extension)
C0601
s
® Selection list 1 ARIT2
Configuration of analog input
signals
1 ARIT2−IN1
1000
FIXED0%
2 ARIT2−IN2
1000
FIXED0%
C0602
g
−199.99
{0.01 %}
199.99 ARIT2
Display of analog input signals
1 ARIT2−IN1
2 ARIT2−IN2
C0606 MONIT OC8
2
0
2
3
TRIP
Warning
Off
OC8 monitoring
Configuration of the I
2
× t
advance warning
l
The threshold is set in C0127