Commissioning – Lenze EVS9332xP User Manual
Page 214

Commissioning
Parameter set management
Saving of parameter set
6.12
6.12.1
l
6.12−2
EDSVS9332P EN 5.0−07/2013
A parameter set transfer can only be executed if controller inhibit is
activated.
}
Danger!
Uncontrolled motor movement possible.
The controller is reinitialised by the parameter set transfer from
the PC to the controller. System configurations and terminal
assignments may be different.
Possible consequences:
ƒ
Severe injuries to persons in or near the machine.
ƒ
The machine is damaged or destroyed.
Protective measures:
ƒ
Make sure that your wiring and drive configuration comply
with the settings of the parameter set.
ƒ
Use terminal X5/28 or the STOP function in GDC as the source
for controller inhibit.
How to transfer a parameter set to the controller:
1. Execute Drive parameters
è Write parameter set to drive.
– Alternatively the command can be executed via key "F5".
2. Open the "Load / Save" menu in the parameter menu and save the
parameter set safe against mains failure with C0003 = 1.
Save parameter set to the
controller