Commissioning – Lenze EVS9332xP User Manual

Page 229

background image

Commissioning

Commissioning examples

6

6.16

l

6.16−3

EDSVS9332P EN 5.0−07/2013

The table shows the commissioning procedure of a positioning in short form,
using the example in Fig. 6.16−1.

Section

Step

See also

Switch on
controller

1. Inhibit controller (X5/28 = LOW).
2. Set X5/E1, X5/E2 to HIGH level.
3. Set X5/E3, X5/E4, X5/E5 to LOW level.
4. Switch on mains:

– The controller is ready for operation after approx. 1 s (2 s

for drives with SinCos encoder with serial interface).

^ 6.3−1

Switch on PC

Start GDC on the PC

– Set the communication parameters for the online mode in

the "Current drive" dialog box.

– Select the controller in the "Assign device description"

dialog box.

Carry out basic
settings

1. Adapt the controller to the mains.

^ 6.5−1

2. Adapt the controller to the motor.

^ 6.5−3

3. Enter machine parameters.

^ 6.5−2

Manual control 1. Enter parameters for manual control or use Lenze setting.

^ 6.10−1

2. Carry out functional test with manual control.

^ 6.10−2

Enter
parameters for
travel profile

1. Enter positioning data in the "Programming" dialog box.
2. Connect the X5 terminals in the "Terminal monitor 93XX

(digital)" menu.
– For internal voltage supply, assign "FIXED1" to X5/A1.

Approx. 24 V are then output at X5/A1.

TIP!
For this application case, use a predefined configuration in
C0005.
C0005 = XXX1X automatically assigns FIXED1 to output X5/A1
(e.g. 20010 = absolute positioning with control via terminals).

^ 6.11−1

Control drive

1. Check whether the controller is ready for operation:

– When the green LED is blinking: Controller is ready for

operation, proceed with step 2.

– When the green LED is off and the red LED is blinking: A

fault has occurred. Remove the fault before proceeding
with the commissioning.

2. Enable controller (X5/28 = HIGH).

– Green LED is lit when X5/28 is set to HIGH level and no

other source of the controller inhibit is active.

3. For operation with a fieldbus module, additional settings are

necessary (see Operating Instructions of the fieldbus
module).

The motor will now rotate according to the setpoint speed
specified and the selected direction of rotation.

^ 6.14−1

^ 9−1

Commissioning steps