Code table, Basic configurations, Configuration – Lenze EVS9332xP User Manual
Page 267

Configuration
Code table
8.4
l
8.5−1
EDSVS9332P EN 5.0−07/2013
8.4
Code table
How to read the code table
Column
Abbreviation
Meaning
Code
Cxxxx
Code Cxxxx
l
Parameter value of the code can be defined
differently for each parameter set
l
Parameter value is accepted immediately (ONLINE)
1
Subcode 1 of Cxxxx
2
Subcode 2 of Cxxxx
v
Changed parameter of code or subcode is accepted after pressing
T V
s
Changed parameter of code or subcode is accepted after pressing
T V when
the controller is inhibited
Designation
Designation of the code
Lenze
Lenze setting (value at delivery or after restoring the delivery status with C0002)
à
The column "IMPORTANT" contains additional information
g
The code only displays a value. It cannot be configured.
Selection
1
{%}
99 Min. value
{unit}
max. value
IMPORTANT
−
Short, important explanation
8.5
Basic configurations
Code
Possible settings
IMPORTANT
No.
Designation
Lenze
Selection
C0002
s
PAR LOAD
0
Load parameter set
0
Default setting
Recover Lenze setting
1
Load PS
Load and activate parameter
set saved in the controller
l
Parameter set is loaded
automatically after every
mains connection
11
Load PS 1 externally
Load parameter set from the
keypad to the controller and
activate it
20
Load PS externally
Load all parameter sets from
the keypad to the EEPROM of
the controller
l
The current parameter set in
the RAM of the controller is
overwritten. Save the
parameter set
C0003 PAR SAVE
0
Save parameter set
0
Executed
Saving completed
1
Save PS 1
Save the parameters loaded in
the controller in the parameter
set selected
11
Save externally
Transfer parameter set to the
keypad
C0004 OP DISPLAY
56
0
{1}
1999 Status display
Keypad shows selected code in
the operating level if no other
status messages from C0183
are active