Commissioning
Changing the assignment of the control terminals X5 and X6
Free configuration of digital outputs
6.9
6.9.2
l
6.9−2
EDSVS9332P EN 5.0−07/2013
ƒ Terminals (X5/E1 ... X5/E5):
– HIGH = +12 V ... +30 V
– LOW = 0 V ... +3 V
ƒ Response times: 1 ms
In C0114 you can define the active signal level (HIGH level active or LOW level
active) for the terminals X5/E1 ... X5/E5.
Example
ƒ C0114/3 =1
ð LOW level at X5/E3 activates JOG2
6.9.2
Free configuration of digital outputs
ƒ The digital outputs X5/A1 ... X5/A4 can be freely linked with internal
digital signals.
ƒ One signal source can be linked with several targets.
The digital outputs can be linked with internal digital signals by entering the
selection figure of the internal signal into corresponding subcode of C0117.
Example
ƒ C0117/2 = 505
ð signal source for X5/A2 is the status message
"direction of rotation" (DCTRL−CW/CCW)
ƒ Terminals (X5/A1 ... X5/A4):
– HIGH = +12 V ... +30 V
– LOW = 0 V ... +3 V
ƒ Response times: 1 ms
In C0118 you can define the active signal level (HIGH level active or LOW level
active) for the terminals X5/A1 ... X5/A4.
Example
ƒ C0118/2 =1
ð With LOW level at X5/A2 the motor rotates in CW
direction (with in−phase motor connection)
Signal level
Inverting the signal level
Description
Linking signals
Signal level
Inverting the signal level