8 Adjustments

8-52

The monitor factor can be changed by setting parameters Pn006.2 and Pn007.2.

The analog monitor output voltage is ±8 V (maximum). The output will be limited to ±8 V even if this value is exceeded
in the above calculations.

Parameter

Multiplier

Remarks

Pn006
Pn007

n.

0

×

1

Factory Setting

n.

1

×

10

n.

2

×

100

n.

3

×

1/10

n.

4

×

1/100

Pn550

Analog Monitor 1 Offset Voltage

Setting Range

Setting Unit

Factory Setting

Setting Validation

-1000.0 to 1000.0

0.1 V

0.0 V

Immediately

Pn551

Analog Monitor 2 Offset Voltage

Setting Range

Setting Unit

Factory Setting

Setting Validation

-1000.0 to 1000.0

0.1 V

0.0 V

Immediately

Example

If Pn006 = 0102, Pn422 = 10.0 [

%], and Pn550 = 3.0 [V], then

Analog Monitor 1 = Torque reference
= {(-1)

× (Torque reference[%]-10%) × 10} + 3[V]

If the torque is 2

%,

= {(-1)

× (52 [%]-10 [%]) ×

× 10} + 3 [V]= -7.2 [V] (Analog Monitor 1 output voltage)

Speed

Position

Torque

Speed

Position

Torque

1 [V]

100 [

%]

INFO