beautypg.com

3) using noise filters, 20 (3) using noise filters – Yaskawa SGDS Sigma III Servo Amplifier User Manual

Page 123

background image

5 Wiring

5.6.2 Wiring for Noise Control

5-20

(3) Using Noise Filters

Use an inhibit type noise filter to prevent noise from the power supply line. The following table lists
recommended noise filters for each SERVOPACK model.

Install a noise filter on the power supply line for peripheral equipment as necessary.

Note: Recommended noise filter is manufactured by SCHAFFNER.

The precautions in using noise filter

Always observe the following installation and wiring instructions. Incorrect use of a noise filter halves its
benefits.
1. Do not put the input and output lines in the same duct or bundle them together.

Table 5.2 Noise Filters

Main Circuit

Power

SERVOPACK Model

Recommended Noise Filter

Capacity (kW)

SGDS-

Model

Specifications

Single-
phase
100 V

0.05

A5F

FN2070-6/07

Single-phase AC 250 V, 6 A

0.10

01F

0.20

02F

FN2070-10/07

Single-phase AC 250 V, 10 A

0.40

04F

FN2070-16/07

Single-phase AC 250 V, 16 A

Single-
phase
200 V

0.05

A5A

FN2070-6/07

Single-phase AC 250 V, 6 A

0.10

01A

0.20

02A

0.40

04A

FN2070-10/07

Single-phase AC 250 V, 10 A

0.80

08A

FN2070-16/07

Single-phase AC 250 V, 16 A

Three-
phase
200 V

0.5

05A

FN258L-7/07

Three-phase AC 480 V, 7 A

1.0

10A

FN258L-16/07

Three-phase AC 480 V, 16 A

IMPORTANT

Noise

Filter

Noise

Filter

Noise

Filter

Incorrect

Correct

Noise

Filter

Separate these circuits

Box

Box

Box

Box