3 atca-9305 setup, 1 power requirements, Table 2-2 – Artesyn ATCA-9305 User's Manual (May 2014) User Manual
Page 62: Typical power requirements

Setup
ATCA-9305 User’s Manual (10009109-07)
62
BT FLASH: If BOOT shunt is installed (booting from local bus), this shunt determines whether
the boot is from local flash or socket. When this BT FLASH shunt is installed, the ATCA-9305
boots from flash. Otherwise, it boots from the socket.
2.3
ATCA-9305 Setup
You need the following items to set up and check the operation of the Artesyn ATCA-9305:
ATCA chassis and power supply
MPC8548 Console cable for EIA-232 port, Artesyn part # C0007662-00
Computer terminal
Save the antistatic bag and box for future shipping or storage.
2.3.1
Power Requirements
Make sure that the blade is used in an AdvancedTCA shelf connected to —48 VDC up to —60
VDC, according to Telecommunication Network Voltage (TNV-2). A TNV-2 circuit is a circuit
whose normal operating voltages exceed the limits for a safety-extra-low-voltage (SELV) under
normal operating conditions, and which is not subject to over-voltages from
telecommunication networks.
Table 2-2 Typical Power Requirements
Configuration
Power
1.0 GHz MPC8548 and 800 MHz Cavium processors, board running at
room temperature with all processors at U-Boot prompt
165 W
RTM-ATCA-9305 I/O
30 W
Rated Voltage
—48 VDC to —60 VDC
US and Canada: —48 VDC
Operating Voltage
—40 VDC to —72 VDC
US and Canada: —48 VDC