Page 90

background image

Chapter 4 Parameters|

Revision Nov. 2008, VLE1, SW V1.03 4-35

01-24

01-25

01-26

01-27

Frequency

Time

01-29

Switch Frequency for S3/S4 Changes to S5

Unit: 0.01

Control

mode

VF

VFPG

SVC

FOCPG FOCPM

Factory setting: 0.00

Settings

0.00~120.00Hz

It is used to set the switch frequency between S4 and S5 for smooth stop.

It is recommended to set this parameter to the leveling speed of elevator.

F requenc y

01-12
accel. time

01-13
decel. time

Time

01-25=S2

01-26=S3

01-24=S1

01-27=S4

01-30=S5

01-29
Switch fr equency

for S3/S 4 changes
to S5

01-28

Mode Selection when Frequency< Fmin

Control

mode

VF

VFPG

SVC

Factory setting: 0

Settings

0

Output

Waiting

1

Zero-speed operation

2

Fmin (4th output frequency setting)

When the AC motor drive is at 0Hz, it will operate by this parameter.

When it is set to 1 or 2, voltage will be output by Fmin corresponding output voltage.

01-31

Deceleration Time when Operating without RUN

Command

Unit: 0.01

Control

mode

VF

VFPG

SVC

FOCPG FOCPM

Factory setting: 2.00

Settings

0.00~600.00

Sec