Delta Electronics Elevator Drive VFD-VL User Manual
Page 131

Chapter 4 Parameters|
4-76
Revision Nov. 2008, VLE1, SW V1.03
07-05
Start-Point for DC Brake
Unit: 0.01
Control
mode
VF
VFPG
SVC
FOCPG
Factory Setting: 0.00
Settings
0.00 to 120.00Hz
This parameter determines the frequency when DC Brake will begin during deceleration. When
the setting is less than start frequency (Pr.01-09), start-point for DC brake will begin from the
min. frequency.
ON
OFF
01-09
07-05
Output freque ncy
Run /Stop
Time
DC Brake Time
DC Brake Time
during St opping
Start
frequen cy
Start-point for
DC brake
time during
stopping
07-0 3
07-0 4
07-06
DC Brake Proportional Gain
Unit: 1
Control
mode
VF
VFPG
SVC
Factory Setting: 50
Settings
1 to 500Hz
It is used to set the output voltage gain when DC brake.
07-07
Dwell Time at Accel.
Unit: 0.01
Control
mode
VF
VFPG
SVC
FOCPG FOCPM
Factory Setting: 0.00
Settings
0.00 to 600.00 sec
07-08
Dwell Frequency at Accel.
Unit: 0.01
Control
mode
VF
VFPG
SVC
FOCPG FOCPM
Factory Setting: 0.00
Settings
0.00 to 120.00 Hz
07-09
Dwell Time at Decel.
Unit: 0.01
Control
mode
VF
VFPG
SVC
FOCPG FOCPM
Factory Setting: 0.00
Settings
0.00 to 600.00 sec
07-10
Dwell Frequency at Decel.
Unit: 0.01
Control
mode
VF
VFPG
SVC
FOCPG FOCPM
Factory Setting: 0.00
Settings
0.00 to 120.00 Hz
In the heavy load situation, Dwell can make stable output frequency temporarily.