Chapter 4 Parameters|

4-76

Revision Nov. 2008, VLE1, SW V1.03

07-05

Start-Point for DC Brake

Unit: 0.01

Control

mode

VF

VFPG

SVC

FOCPG

Factory Setting: 0.00

Settings

0.00 to 120.00Hz

This parameter determines the frequency when DC Brake will begin during deceleration. When

the setting is less than start frequency (Pr.01-09), start-point for DC brake will begin from the

min. frequency.

ON

OFF

01-09

07-05

Output freque ncy

Run /Stop

Time

DC Brake Time

DC Brake Time
during St opping

Start
frequen cy

Start-point for
DC brake

time during
stopping

07-0 3

07-0 4

07-06

DC Brake Proportional Gain

Unit: 1

Control

mode

VF

VFPG

SVC

Factory Setting: 50

Settings

1 to 500Hz

It is used to set the output voltage gain when DC brake.

07-07

Dwell Time at Accel.

Unit: 0.01

Control

mode

VF

VFPG

SVC

FOCPG FOCPM

Factory Setting: 0.00

Settings

0.00 to 600.00 sec

07-08

Dwell Frequency at Accel.

Unit: 0.01

Control

mode

VF

VFPG

SVC

FOCPG FOCPM

Factory Setting: 0.00

Settings

0.00 to 120.00 Hz

07-09

Dwell Time at Decel.

Unit: 0.01

Control

mode

VF

VFPG

SVC

FOCPG FOCPM

Factory Setting: 0.00

Settings

0.00 to 600.00 sec

07-10

Dwell Frequency at Decel.

Unit: 0.01

Control

mode

VF

VFPG

SVC

FOCPG FOCPM

Factory Setting: 0.00

Settings

0.00 to 120.00 Hz

In the heavy load situation, Dwell can make stable output frequency temporarily.