Delta Electronics Elevator Drive VFD-VL User Manual
Page 114

Chapter 4 Parameters|
Revision Nov. 2008, VLE1, SW V1.03 4-59
05-06
Rs of Motor
Unit: 0.001
Control
mode
SVC
FOCPG
TQCPG
Factory setting: 0.000
05-07
Rr of Motor
Unit: 0.001
Control
mode
SVC
FOCPG
TQCPG
Factory setting: 0.000
Settings
0.000~65.535
Ω
05-08
Lm of Motor
Unit: 0.1
Control
mode
SVC
FOCPG
TQCPG
Factory setting: 0.0
05-09
Lx of Motor
Unit: 0.1
Control
mode
SVC
FOCPG
TQCPG
Factory setting: 0.0
Settings
0.0~6553.5mH
05-10
Torque Compensation Time Constant
Unit: 0.001
Control
mode
SVC
Factory setting: 0.020
Settings
0.001 to 10.000 sec
05-11
Slip Compensation Time Constant
Unit: 0.001
Control
mode
SVC
Factory setting: 0.100
Settings
0.001 to 10.000 sec
Setting Pr.05-10 and Pr.05-11 change the response time for the compensation.
When Pr.05-10 and Pr.05-11 are set to 10 seconds, its response time for the compensation
will be the longest. But if the settings are too short, unstable system may occur.
05-12
Torque Compensation Gain
Unit: 1
Control
mode
VF
VFPG
Factory setting: 0
Settings
0
to10
This parameter may be set so that the AC motor drive will increase its voltage output to obtain
a higher torque.
05-13
Slip Compensation Gain
Unit: 0.01
Control
mode
SVC
VFPG
SVC
Factory setting: 0.00
Settings
0.00
to10.00