Chapter 4 Parameters|

Revision Nov. 2008, VLE1, SW V1.03 4-59

05-06

Rs of Motor

Unit: 0.001

Control

mode

SVC

FOCPG

TQCPG

Factory setting: 0.000

05-07

Rr of Motor

Unit: 0.001

Control

mode

SVC

FOCPG

TQCPG

Factory setting: 0.000

Settings

0.000~65.535

Ω

05-08

Lm of Motor

Unit: 0.1

Control

mode

SVC

FOCPG

TQCPG

Factory setting: 0.0

05-09

Lx of Motor

Unit: 0.1

Control

mode

SVC

FOCPG

TQCPG

Factory setting: 0.0

Settings

0.0~6553.5mH

05-10

Torque Compensation Time Constant

Unit: 0.001

Control

mode

SVC

Factory setting: 0.020

Settings

0.001 to 10.000 sec

05-11

Slip Compensation Time Constant

Unit: 0.001

Control

mode

SVC

Factory setting: 0.100

Settings

0.001 to 10.000 sec

Setting Pr.05-10 and Pr.05-11 change the response time for the compensation.

When Pr.05-10 and Pr.05-11 are set to 10 seconds, its response time for the compensation

will be the longest. But if the settings are too short, unstable system may occur.

05-12

Torque Compensation Gain

Unit: 1

Control

mode

VF

VFPG

Factory setting: 0

Settings

0

to10

This parameter may be set so that the AC motor drive will increase its voltage output to obtain

a higher torque.

05-13

Slip Compensation Gain

Unit: 0.01

Control

mode

SVC

VFPG

SVC

Factory setting: 0.00

Settings

0.00

to10.00