Chapter 4 Parameters|

Revision Nov. 2008, VLE1, SW V1.03 4-81

07-28

Emergency Stop (EF) & Forced Stop Selection

Control

mode

VF

VFPG

SVC

FOCPG TQCPG FOCPM

Factory Setting: 0

Settings

0

Coast

to

stop

1 By deceleration Time 1

2 By deceleration Time 2

3 By deceleration Time 3

4 By deceleration Time 4

5

By

Pr.01-31

When the multi-function input terminal is set to 10 or 14 and it is ON, the AC motor drive will be

operated by Pr.07-28.

07-29

Time for Decreasing Torque at Stop

Unit: 0.001

Control

mode

FOCPG

TQCPG

FOCPM

Factory Setting: 0.000

Settings

0.000 to 1.000 sec

It is used to set the time for decreasing torque to 0%.

RUN/STOP

0%

i

t

i

00-01 x

100%

300% x (07-29)=t