Chapter 4 Parameters|

4-62

Revision Nov. 2008, VLE1, SW V1.03

Group 6 Protection Parameters

06-00

Low Voltage Level

Unit: 0.1

Control

mode

VF

VFPG

SVC

FOCPG TQCPG FOCPM

Settings 230V series 160.0~220.0Vdc

Factory Setting: 180.0

460V series 320.0~440.0Vdc

Factory Setting: 360.0

It is used to set the Lv level.

LV

Pr. 06-00

30V(60V)

input voltage

06-01

Phase-loss Protection

Control

mode

VF

VFPG

SVC

FOCPG TQCPG FOCPM

Factory setting: 2

Settings

0

Warn and keep operation

1

Warn and ramp to stop

2

Warn and coast to stop

It is used to set the phase-loss treatment. The phase-loss will effect driver’s control

characteristic and life.

06-02

Over-Current Stall Prevention during Acceleration

Unit: 1

Control

mode

VF

VFPG

SVC

Factory setting: 00

Settings

00~250% (00: disable)

During acceleration, the AC drive output current may increase abruptly and exceed the value

specified by Pr.06-02 due to rapid acceleration or excessive load on the motor. When this

function is enabled, the AC drive will stop accelerating and keep the output frequency constant

until the current drops below the maximum value.