Chapter 6 Fault Code Information and Maintenance|

Revision Nov. 2008, VLE1, SW V1.03 6-11

6.2 Maintenance and Inspections

Before the check-up, always turn off the AC input power and remove the cover. Wait at least 10

minutes after all display lamps have gone out, and then confirm that the capacitors have fully
discharged by measuring the voltage between DC+ and DC-. The voltage between DC+ and DC-
should be less than 25VDC.

„

Ambient environment

Maintenance

Period

Check Items

Methods and Criterion

Daily

Half

Year

One

Year

Check the ambient temperature,
humidity, vibration and see if
there are any dust, gas, oil or
water drops

Visual inspection and measurement
with equipment with standard
specification

{

If there are any dangerous
objects

Visual inspection

{

„

Voltage

Maintenance

Period

Check Items

Methods and Criterion

Daily

Half

Year

One

Year

Check if the voltage of main
circuit and control circuit is
correct

Measure with multimeter with standard
specification

{

„

Keypad

Maintenance

Period

Check Items

Methods and Criterion

Daily

Half

Year

One

Year

Is the display clear for reading

Visual inspection

{

Any missing characters

Visual inspection

{