Chapter 4 Parameters|

Revision Nov. 2008, VLE1, SW V1.03 4-65

06-10

Over-torque Detection Time (OT2)

Unit: 0.1

Control

mode

VF

VFPG

SVC

FOCPG TQCPG FOCPM

Factory setting: 0.1

Settings

0.0 to 60.0 sec

Pr.06-05 and Pr.06-08 determine the operation mode of the drive after the over-torque is

detected via the following method: if the output current exceeds the over-torque detection level

(Pr.06-06) and also exceeds the Pr.06-07 Over-Torque Detection Time, the fault code

“OT1/OT2” is displayed. If a Multi-Functional Output Terminal is to over-torque detection, the

output is on. Please refer to Pr.02-11~02-22 for details.

5%

Pr.06-06,
Pr.06-09

Pr.06-07, 06-10

current

06-11

Current Limit

Unit: 1

Control

mode

FOCPG

TQCPG

Factory setting: 150

Settings

0 to 250%

It is used to set the current limit.

06-12

Electronic Thermal Relay Selection

Control

mode

VF

VFPG

SVC

FOCPG TQCPG FOCPM

Factory setting: 2

Settings

0

Inverter

motor

1

Standard

motor

2

Disabled

It is used to prevent self-cooled motor overheats under low speed. User can use electrical

thermal relay to limit driver’s output power.

06-13

Electronic Thermal Characteristic

Unit: 0.1

Control

mode

VF

VFPG

SVC

FOCPG TQCPG FOCPM

Factory setting: 60.0

Settings

30.0 to 600.0 sec