Model 5820XL / 5820XL-EVS Installation Manual

LS10061-001SK-E

6-3

6.

Select one of the following options from the menu that displays.

1 - Review System

Press 1 if you need to review the JumpStart configuration.

2 - Repeat JumpStart

Press 2 if you need to rerun JumpStart for any reason.

3 - Accept Configuration

1. If you are ready to make the JumpStart configuration permanent, select 3.

2. The system will ask you if the installation contains duct detectors. If there are none,

select 2 for No and skip to Step 8. If the system contains duct detectors, select 1 for Yes
and continue with Step 3.

3. From the list that displays, select the SLC that contains the duct detectors.

4. The first photoelectric or ionization detector on the system will display. Select 1 for

DUCT and 2 for NonDUCT.

5. Press

to select the next detector. Select 1 for DUCT and 2 for NonDUCT. Continue

until all duct detectors have been selected. (Note: You can move backwards through the

list with

).

6. When you reach the last detector on this device, press the left arrow.

7. The system will ask you if there are more duct detectors in the system. If there are, select

1 for Yes and repeat from Step 3. If there are no more duct detectors, select 2 for No and
continue with
Step 8.

8. The system will restart in 10 seconds. You can press 1 to restart immediately.

9. After the system resets, it will use the new JumpStart configuration.

4 - Enter Programming

If you want to go directly to Program Mode to configure any devices, press 4. The
Programming Menu appears and you can begin programming.