SilentKnight 5824 Serial/Parallel Module User Manual

Specifications compatibility, Mounting

background image

P/N 151392 Rev G2

ECN: 12-207

5824 Serial/Parallel Printer
Interface Module Installation
Instructions

The 5824 Serial/Parallel Printer Interface
Module (5824) connects a compatible fire alarm
control panel (FACP) directly to a printer to
print event history. You can also print system
event logs in real time and detector status from
addressable FACPs.

Note: Installation and wiring of this device must be done in

accordance with NFPA 72 and local ordinances.

Specifications

Compatibility

The 5824 is compatible with all Silent Knight
addressable FACPs and with the 5208
conventional FACP.

Mounting

The 5824 comes in a plastic enclosure which
must be mounted inside the annunciator or
accessory cabinet.

To mount the 5824 plastic enclosure into the
appropriate cabinet:

1. Remove the 5824 cover. Use a small screw

driver if necessary.

2. Remove the 5824 circuit board from the base

by pushing outward on the base snap
retaining tabs and lifting the circuit board
out.

Figure 1: 5824 Circuit Board And Plastic Base

3. Mount the plastic base into the appropriate

accessory cabinet.

4. Replace the circuit board in the plastic base.

Note: It may be necessary to connect the wiring to the circuit

board before the board is replaced into the base.

Operating Voltage: 24 VDC

Current (Alarm and Standby): 50 mA

Max Per FACP Addressable FACPs: 8; 5208 FACP: 1

Ambient Temperature: 32°F to 120°F (0°C to 49°C)

Max Wiring Distance from FACP: 6000 ft. (1829 m)

Mounting: Surface

Dimensions: 6”W x 7-3/4”H x 1-7/16”D
(15.2 cm W x 19.7 cm H x 3.7 cm D)

Parallel Port: Ancillary

Serial Port: Primary Fire Signaling