Model 5820XL / 5820XL-EVS Installation Manual

LS10061-001SK-E

8-5

All four lines of the LCD are not full.

This test takes approximately 15 seconds to complete. You can press any key to end manually while the test is
still in progress. When the test ends, you will be returned to the .

8.5.8

Conduct a Walk Test

1.

From the Main Menu, press 1 for System Tests.

2.

Select 3 for Walk Test-No Report. The LCD will display “WALK TEST STOPPED” on Line 1 and “ENTER
= start test” on Line 3. Enter the time period you wish the NAC circuit to be active for each alarm (06 to 180
seconds). If you select this option, central station reporting will be disabled while the test is in progress.

Or
Select 4 for Walk Test-with Report. The LCD will display “WALK TEST STOPPED” on Line 1 and
“ENTER = start test” on Line 3. Enter the time period you wish the NAC circuit to be active for each alarm
(06 to 180 seconds). If you select this option, central station reporting will occur as normal during the walk
test.
The panel generates a TEST report to the central station when the walk test begins. During a walk test, the
panel’s normal fire alarm function is completely disabled, placing the panel in a local trouble condition. All
zones respond as 1-Count zones (respond when a single detector is in alarm) during a walk test. Each alarm
initiated during the walk test will be reported and stored in the event history buffer.

3.

Press ENTER to end the walk test. The system will reset. The panel will send a “TEST RESTORE” report to
the central station.

If you do not end the walk test manually within four hours, it will end automatically.

If an alarm or pre-alarm condition is occurring in the system, you will not be able to enter the walk test.

Note: The panel does not do a full 30 second reset on resettable power outputs. As soon as the device is back to

normal, the panel is ready to go to the next device.

8.5.9

Conduct a Dialer Test

1.

From the Main Menu, press 1 for System Tests.

2.

Select 5 for Dialer Test. The screen will display “Manual dialer test started”. When the test is completed, you
will be returned to the .

8.5.10

Silence alarms or troubles

Press SILENCE and enter your code or rotate the key at the prompt. If an external silence switch has been
installed, activating the switch will silence alarms or troubles. If you are already using system menus when you
press SILENCE, you will not need to enter your code or rotate the key.

Note: Alarm and trouble signals that have been silenced, but the detector remains un-restored, will un-silence

every 24 hours until the detector is restored.

Note: For EVS system, pressing silence at an LOC will only silence the System in Control. See Section 9.8.1.

8.5.11

Reset alarms

Press RESET and enter your code or rotate the key at the prompt. If an external reset switch has been installed,
activating the switch will reset alarms.

Note: For EVS Systems, pressing reset at an LOC will prompt asking which system to reset.

IMPORTANT!

If any alarm verification zones are being used, the user will be asked if they wish to disable alarm
verification during walk test. This occurs for either walk test option.