2 slc multiple locator – SilentKnight 5820XL User Manual
Page 201

LS10061-001SK-E
Testing and Troubleshooting
11-4
A message similar to the one shown in Figure 11-1 will display.
Figure 11-1 Shut Down Warning
3.
Press the
or
arrow to toggle NO to YES then press ENTER.
If NO is chosen you will exit back to the Point Function menu.
If Yes is chosen the system will cease normal operation leaving the premise unprotected.
4.
Select the SLC loop.
5.
Enter the SLC address of the device you wish to locate.
The LED on the selected device will start flashing.
6.
Press the left arrow to exit the SLC Device Locator.
Note: Once you exit, the system will resume normal operation.
11.5.2
SLC Multiple Locator
This feature is the same as SLC Device Locator, except you can locate up to 8 devices on a single search.
Follow these instructions to locate multiple SLC devices:
1.
Select 2 (Point Functions) from the Main Menu.
2.
Select 5 (SLC Multiple Device Locator).
A message similar to the one shown in Figure 11-1 will display.
Figure 11-2 Shut Down Warning
3.
Press the
or
arrow to toggle NO to YES then press ENTER.
If NO is chosen you will exit back to the Point Function menu.
If Yes is chosen the system will cease normal operation leaving the premise unprotected.
4.
Select the SLC loop.
5.
Enter up to 8 SLC addresses for the devices you wish to locate.
The LEDs on the selected devices will start flashing.
6.
Press the left arrow to exit SLC Multiple Device Locator.
Note: Once you exit, the system will resume normal operation.