Commands. table 9-3 – SilentKnight 5820XL User Manual
Page 186

LS10061-001SK-E
Emergency Voice System Operation
9-22
Zone Mapping to Voice Output Groups
When a voice output group is selected to be activated by a zone, the cadence pattern choice listed in Section
7.3.1.4 do not apply. For voice output groups, one of 18 plus all “Aux Voice In” system wide voice commands
will activate instead of the cadence pattern. Which command is determined by the event type selected for that
zone. The voice commands are programmable by the installer (see Section 7.10 for more information). Table 9-3
lists the voice commands and the associated event type.
*The priorities are not set, the are configurable by the user. For each installation a risk assessment must be done
to decide the priority of events.
Table 9-3: Event Types for Voice Commands
Priority*
Name
Comments
1
Fire
It will sound whenever a request is made to activate a voice output
group that was triggered from a manual pull, detector, or water flow
event.
2
Fire Aux1
Fire Command
3
Fire Aux 2
Fire Command
4
Fire Pre Alarm
Fire Command
5
Fire Supervisory
Fire Command
6
CO Alarm
CO Command
7
CO Supervisory
CO Command
8
Custom Emergency Comm
Custom EVS command (Microphone triggered EVS)
9
Emergency Communication 1
EVS Message 1
10
Emergency Communication 2
EVS Message 2
11
Emergency Communication 3
EVS Message 3
12
Emergency Communication 4
EVS Message 4
13
Emergency Communication 5
EVS Message 5
14
Emergency Communication 6
EVS Message 6
15
Emergency Communication 7
EVS Message 7
16
Emergency Communication 8
EVS Message 8
17
Aux Voice In 1
First EVS-VCM/RVM configured as lowest SBUS Address.
18 - XX
Aux Voice in 2 - XX
Remaining EVS-VCM/RVM configured as next lowest SBUS Address.
XX
General Emergency Communication
General EVS - Active when any other EVS is active in system
XX
Trouble
Fire Command