Zone Mapping to Voice Output Groups

When a voice output group is selected to be activated by a zone, the cadence pattern choice listed in Section
7.3.1.4 do not apply. For voice output groups, one of 18 plus all “Aux Voice In” system wide voice commands
will activate instead of the cadence pattern. Which command is determined by the event type selected for that
zone. The voice commands are programmable by the installer (see Section 7.10 for more information). Table 9-3
lists the voice commands and the associated event type.

*The priorities are not set, the are configurable by the user. For each installation a risk assessment must be done
to decide the priority of events.

Table 9-3: Event Types for Voice Commands

Priority*

Name

Comments

1

Fire

It will sound whenever a request is made to activate a voice output
group that was triggered from a manual pull, detector, or water flow
event.

2

Fire Aux1

Fire Command

3

Fire Aux 2

Fire Command

4

Fire Pre Alarm

Fire Command

5

Fire Supervisory

Fire Command

6

CO Alarm

CO Command

7

CO Supervisory

CO Command

8

Custom Emergency Comm

Custom EVS command (Microphone triggered EVS)

9

Emergency Communication 1

EVS Message 1

10

Emergency Communication 2

EVS Message 2

11

Emergency Communication 3

EVS Message 3

12

Emergency Communication 4

EVS Message 4

13

Emergency Communication 5

EVS Message 5

14

Emergency Communication 6

EVS Message 6

15

Emergency Communication 7

EVS Message 7

16

Emergency Communication 8

EVS Message 8

17

Aux Voice In 1

First EVS-VCM/RVM configured as lowest SBUS Address.

18 - XX

Aux Voice in 2 - XX

Remaining EVS-VCM/RVM configured as next lowest SBUS Address.

XX

General Emergency Communication

General EVS - Active when any other EVS is active in system

XX