3 evs system options, 1 enable evs system, Section 7.10.3.1 – SilentKnight 5820XL User Manual
Page 144
LS10061-001SK-E
Programming
7-36
7.3.1.4 do not apply. For voice output groups, one of seventeen system wide voice commands will activate
instead of the cadence pattern. Which command is determined by the event type selected for that zone. This
menu option allows you to program, the message to be used, the tone used, repeats, and message delays, for each
of the seventeen commands. Table 9-3 lists the seventeen different commands and the associated event type. See
also Section 7.3.1 for more information.
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Program Menu.
3.
Select 9 for Voice Options.
4.
Select 2 for Edit Voice Cmds.
5.
Select the command you wish to edit:
•
Fire Alarm
•
Fire Aux1
•
Fire Aux2
•
Alarm CO
•
Fire Supervisory
•
CO Alarm
•
CO Supervisory
•
Trouble
•
Custom Emergency Comm
•
Emergency Comm 1 thru 8
6.
Select the desired message used for that command.
7.
Select the tone to be played between messages. (ANSI, March Code, California, Steady, Alert Tone, High-
Lo, ANSI Whoop, Cont Whoop, Temporal 4, Temp 4 520Hz, ANSI 520Hz, Steady 520Hz, No Tones).
Note: 520Hz tones are available when using EVS-100W or EVS-INT50W. See Table A-3 for a list of compatible
speakers.
8.
Select how many times you wish the message to repeat. (None, 1 - 14, or Continuous).
9.
Enable/Disable AMR (Allow Message to Repeat with New Group Activation). Y = Yes, N = No.
10. Select the initial delay time (0 to 28, or 3 seconds, in 4 second increments).
11. Select the inter message delay time (4 to 32 seconds, in 4 second increments).
7.10.3
EVS System Options
7.10.3.1
Enable EVS System
1.
Select 7 for Program Menu.
2.
Select 9 for Voice Options.
3.
Select 3 for EVS System Options.
4.
Then select 1 for Enable EVS System.
5.