SilentKnight EVS-CE4 User Manual
Evs-ce4 installation instructions, Compatibility, Board layout & mounting
P/N LS10070-001SK-E Rev A1
ECN 13-0704
EVS-CE4 Installation Instructions
The EVS-CE4 adds four audio circuits to the
EVS-50W or EVS-125W. The EVS-CE4
mounts inside the EVS-50W or EVS-125W
cabinet
Note: Installation and wiring of this device must be done in
accordance with NFPA 72 and local ordinances.
Compatibility
The EVS-CE4 is compatible with the
IntelliKnight 5820XL-EVS. For more
information, refer to Installation manual for
5820XL-EVS (PN LS10061-001SK-E).
Board Layout & Mounting
1. Remove AC power from the EVS-50W or
EVS-125W control panel and disconnect
the backup batteries.
2. Using the four supplied screws, mount
the EVS-CE4 in the EVS-50W or EVS-
125W cabinet as shown in Figure 1.
Figure 1: Mounting the EVS-CE4
Specifications
Standby Current: 20 mA
Alarm Current: 180 mA
Wiring
1. Connect the supplied audio expander
cable harness (PN 130426) from the
connector labeled Audio Expander on
the EVS-50W or EVS-125W to the
connector on the EVS-CE4.
See Figure 2.
Figure 2: Audio Expander Wire Harness Connections
2. Wire speakers for Class B (Style Y)
supervision as shown in Figure 3 or for
Class A (Style Z) wiring as shown in
Mounting
Screws
Mounting
Screws
EVS-CE4
Connector
EVS-50W
Audio
Expander