beautypg.com

2 city box connection using the 5220 module – SilentKnight 5820XL User Manual

Page 65

background image

LS10061-001SK-E

Control Panel Installation

4-32

5.

Program Flexput circuit 6 for supervisory non latching.

Figure 4-40 Keltron 3158 Connection to Control Panel

4.14.2

City Box Connection Using the 5220 Module

This section describes how to connect the control panel to a local energy municipal fire alarm box or “city box”
as required by NFPA 72 Auxiliary Protected Fire Alarm systems for fire alarm service. The city (master) box is
an enclosure that contains a manually operated transmitter used to send an alarm to the municipal
communication center which houses the central operating part of the fire alarm system.

City Box Standby Current: 0 (Notification supervision current accounted for in control panel draw).

Alarm Current: 1 Amp for 1 second 27.2 VDC max

The maximum coil and wire resistance (combined) must not exceed 30 ohms.

To install the 5220 for city box connection:

1.

Use one of the knockouts on the right side of the control panel to connect the 5220 using a short piece of
conduit (must not exceed 20 feet in length).

2.

Wire the 5220 to the control panel as shown in Figure 4-41. This drawing also shows how to connect the city
box coil to terminals 3 and 4 on the 5220. Do not install an EOL resistor in the terminals of the Flexput cir-
cuit used for this application.

3.

Connect earth ground wire to the 5220 chassis with mounting screw.

Table 4-3: Keltron 3158 to Control Panel Connections

Terminal #

Connects To

Terminal #

Connects To

3158 Term. 1

To Keltron receiving equipment

3158 Term. 8

Control panel Term. 28

3158 Term. 2

To Keltron receiving equipment

3158 Term. 9

Control panel Term. 5

3158 Term. 3

Earth ground

3158 Term. 10

Control panel Term. 4

3158 Term. 4

Not used; no connection.

Control panel Term. 6

Control panel Term. 29

3158 Term. 5

Control panel Term. 18

Control panel Term. 28

Control panel Term. 31

3158 Term. 6

Control panel Term. 19

Control panel Term. 29

Control panel Term. 30

3158 Term. 7

Control panel Term. 7

Not suitable for remote station

where separate transmission

supervisory (if applicable), and

protected premise service

circuits are required for fire

trouble signals.

Intended for connection to a
polarity reversal circuit of a
remote station receiving unit
having compatible ratings.

Example

This manual is related to the following products: