SilentKnight 5220 Direct Connect Module User Manual
Specifications mounting
P/N 151409
5220 Direct Connect Module
Installation Instructions
The 5220 is a direct connect module used to
connect a fire alarm control panel (FACP) to a
city box or polarity reversal communicator. The
following instruction are generic installation
instructions, refer to the FACP installation
manual for compatibility and usage.
Note: Installation and wiring of this device must be done in
accordance with NFPA 72 and local ordinances.
Specifications
Mounting
The 5220 comes equipped with its own cabinet
assembly. The 5220 is intended for indoor use
only in a dry location.
1. Remove the cover from the 5220.
2. Mount the 5220 with four screws in the holes
Figure 1: Mounting the 5220
3. Wiring the 5220 as shown in Figure 2.
4. Replace the 5220 cover and secure it with
the two self-tapping screws supplied.
Operating Voltage: 19.4 to 28 VDC
City Box Current : 1 A for 1 Second,
max coil resistance 30 ohms
Polarity Reversal: 20 mA max.,
max loop resistance 3 k ohms
Ambient Temperature: 32°F to 120°F (0°C to 49°C), or
humidity within the range of 10%-93% at 30°C (86°F)
noncondensing.
Dimensions: 6-1/2”W x 1-5/16”H x 2-1/8”D
(16.51 cm W x 3.33 cm H x 5.40 cm D)
Terminal Wire Rating: 12 - 24 AWG
Mounting Holes
Mounting Holes
Cover Screw
Hole
Cover Screw
Hole