13 view status of a point, 14 view alarms, supervisories or troubles, 15 view system information – SilentKnight 5820XL User Manual
Page 153: 16 reset items, 1 reset dialer, 2 reset dsp usb, 17 communicating with a remote computer, 1 reset dialer 8.5.16.2 reset dsp usb

Model 5820XL / 5820XL-EVS Installation Manual
LS10061-001SK-E
8-7
8.5.13
View Status of a Point
1.
From the Main Menu, select 2 for Point Status.
2.
From the list that displays, press ENTER to select the module where this point is located. Next, enter the
point to display. The screen that displays will show you if the point has a trouble and will provide sensitivity
compliance information. (See Section 8.5.12 for complete information about detector sensitivity compli-
ance.)
8.5.14
View Alarms, Supervisories or Troubles
When the system is in alarm, supervisory, or trouble, you can press the down arrow to view the location of an
alarm, supervisory, or trouble.
8.5.15
View System Information
Press 8 from the Main Menu to view the panel model and serial number and system version number and date.
Press the left arrow to return to the main menu.
8.5.16
Reset Items
From the Main Menu, select 6 for Reset Items.
8.5.16.1 Reset Dialer
This options allows the user to Reset the Dialer. The LCD will display:
“Dialer Reset in progress… Please Wait“
You will be returned to the Main Menu when the reset is complete.
8.5.16.2 Reset DSP USB
This options allows the user to reset both the DSP Controller and USB interface logic. The LCD will display:
“Dialer Reset in progress… Please Wait“
You will be returned to the Main Menu when the reset is complete.
8.5.17
Communicating with a Remote Computer
An installer at the panel site can initiate communications between the panel and a computer running SKSS 5660.
You can use this feature to upload a panel configuration. For example, if you have made programming changes to
an installation on site using an annunciator, you can send your changes to the computer, so that the central station
will have the latest data about the installation. See the software manual for more information (PN 151240).
To initiate communication:
1.
From the Main Menu, select 9 for Up/Download.
2.
From the next screen that displays, select the communication device. Options are:
3.
If you are using the panel’s internal modem to communicate, you will be prompted to enter a phone number.
If you are communicating via the RS232 connection, a phone number is not needed and this step will be
skipped.
1 = Internal Modem
If you select this option, you will use the panel’s built-in modem to call the
computer.
2 = RS232 connection
If you select this option, the panel and a computer are both on-site connected via