14 evs timer options, 2 timers include, 3 evs timer menu – SilentKnight 5820XL User Manual
Page 188: 2 timers include 9.14.0.3 evs timer menu

LS10061-001SK-E
Emergency Voice System Operation
9-24
9.14 EVS Timer Options
9.14.0.2 Timers include
•
EVS Control Lockout
•
Immediate
•
Never
•
Timer. (If timer is selected, a range of 1-720 minutes and 0-59 seconds are allowed. Default is 30 sec-
onds).
•
EVS Event Auto Reset Time (including Custom Emergency Communication 0 and Emergency
Communication 1-8).
•
Event Disabled (the event can not be generated)
•
Never
•
Timer (If timer is selected, a range of 0-240 minutes is allowed. Default is Never Reset).
9.14.0.3 EVS Timer Menu
Note: Auto Reset settings only apply to the EVS Events when activated from an LOC interface.
Table 9-5 EVS Timer Menu
EVS Timer
Option
Control Lockout
Immed/Timer/Never
Auto Reset EC0 (Custom EVS Event)
Disabled/Never/Timer (Min XXX)
Auto Reset EC1
Disabled/Never/Timer (Min XXX)
Auto Reset EC2
Disabled/Never/Timer (Min XXX)
Auto Reset EC3
Disabled/Never/Timer (Min XXX)
Auto Reset EC4
Disabled/Never/Timer (Min XXX)
Auto Reset EC5
Disabled/Never/Timer (Min XXX)
Auto Reset EC6
Disabled/Never/Timer (Min XXX)
Auto Reset EC7
Disabled/Never/Timer (Min XXX)
Auto Reset EC8
Disabled/Never/Timer (Min XXX)