beautypg.com

SilentKnight 5820XL User Manual

Page 105

background image

LS10061-001SK-E

Programming Overview

6-26

System
Options

System Event
Outputs

Trouble Events

System
Trouble

Select Group (*None)

Section 7.6.3.1

Select Cadence (*None)

Alarm Silence

Select Group (*None)

Select Cadence (*None)

Trbl Silence

Select Group (*None)

Select Cadence (*None)

User Selected

Group Tr

Select Group
(*None) and

Cadence

(*None)

SBUS Com

SBUS Pwr

SLC Loop

AC Loss

Battery

Gnd Flt

Phone Ln

Account

Printer

Aux Pwr

Sys Sw

Sys Alarm
Cadence

Fire Drill
Cadence

00-21, 23

*00 (Constant)

Section 7.6.3.2

System Aux1
Cadence

00-21, 23

*00 (Constant)

System Aux2
Cadence

00-21, 23

*00 (Constant)

Time Options

Water Flow Delay 0 - 90 Seconds *01

Water Flow
delay is the
number of sec.
before water
flow alarm is
generated.

Section 7.6.4.1

Alarm Verification
time

1 to 250
seconds

*60

Section 7.6.4.2

Low AC Delay

0 - 30 hours

*3

Low AC Report
Delay

Section 7.6.4.3

Clock

AM/PM

*AM/PM

System Clock
Format (AM/
PM or military)

System Clock Format
(AM/PM or military).
Section 7.6.4.4

Military

AC Freq:

50 Hz

Section 7.6.4.5

60 Hz

Neither

Table 6-1: Programming Quick Reference Table

Menu

Options/Defaults(*)

Comments

This manual is related to the following products: