beautypg.com

1 disable / enable nacs by template, 3 disable / enable nacs by group, 1 disable / enable zone points – SilentKnight 5820XL User Manual

Page 150: 4 view event history, 5 to clear the event history, 6 conduct a fire drill, 7 conduct an indicator test

background image

LS10061-001SK-E

System Operation

8-4

8.5.2.1 Disable / Enable NACs by Template

1.

Press 1 for Disable NACs by Template, press 2 to Enable NACs by Template.

2.

Use the

or

arrow to move through the list of templates. Press ENTER to select the current template.

8.5.3

Disable / Enable NACs by Group

1.

Select 1 for Disable/Enable Pt.

2.

Select 3 to Disable NACs by group or 4 to Enable NACs by group.

3.

Use the

or

arrow to move through the list of groups. Press ENTER to select the group highlighted.

8.5.3.1 Disable / Enable Zone Points

1.

Press 5 to Disable Zone Points, press 6 to Enable Zone Points.

2.

Use the

or

arrow to move through the list of zones. Press ENTER to select the zone highlighted.

8.5.4

View Event History

Use the View Event History feature to display events on LCD. From the Main Menu, press 3 to select Event
History. Events will begin displaying with most recent events first.

The panel can store up to 1000 events. When it reaches its 1000-event capacity, it begins deleting, starting with
the oldest events.

If a printer is attached to the system (via a Module 5824 serial/parallel interface module), you can print event
history (see Section 8.5.18).

The 5660 SKSS or 5670 SKSS can be used to retain more than 1000 events and to create event history reports.

8.5.5

To clear the event history

From the main menu select 1 for System Tests. From the test menu select 6 Clear History Buffer.

8.5.6

Conduct a Fire Drill

1.

From the Main Menu, press 1 for System Tests.

2.

Press 1 for Fire Drill. You will be prompted to press ENTER.

3.

The drill will begin immediately after you press ENTER.

4.

Press any key to end the drill. (If you do not press any key to end the fire drill manually, it will time out auto-
matically after ten minutes).

If a fire drill switch has been installed, activating the switch will begin the drill; deactivating the switch will end
the drill.

8.5.7

Conduct an Indicator Test

The indicator test checks the annunciator LEDs, PZT, and LCD display.

1.

From the Main Menu, press 1 for System Tests.

2.

Press 2 for Indicator Test. The system turns on each LED several times, beeping the PZT as it does so. At the
same time it scrolls each available character across the LCD. A problem is indicated if any of the following
occurs:

An LED does not turn on;

You do not hear a beep;