beautypg.com

Using devicenet explicit messaging – Rockwell Automation 2100-GK61 DeviceNet to SCANport User Manual

Page 93

background image

Publication 2100-UM001B-EN-P – January 2001

Chapter

6

Using DeviceNet Explicit
Messaging

Chapter Objectives

Chapter 6 provides information you need to monitor and configure
the SCANport device using explicit messaging on DeviceNet. In this
chapter, you will read about the following:

Required equipment.

Message translations.

Messaging guidelines for the 1771-SDN scanner.

Messaging guidelines for the 1747-SDN scanner.

Example messages.

Using messages to control SCANport products.

Writing to register objects.

Refer to Appendix C, DeviceNet Objects, for information on object
data support.

Required Equipment

Before using messaging, your PC must be:

Running Logix5 and RSLinx if you are using a PLC. Refer to
http://www.software.rockwell.com for more information on these
products.
-OR-
Running RSLogix500 and RSLinx if you are using an SLC. Refer
to http://www.software.rockwell.com for more information on
these products.

Connected to and communicating with the DeviceNet network
using a 1784-PCD card, 1784-PCID, card or a 1770-KFIO
adapter.

Explicit Message Program
Control for PLC-5

Use the Explicit Message Program Control feature to configure
device parameters on your DeviceNet network via the ladder logic
program in the PLC-5 processor that is controlling these devices.

You can use Explicit Message Program Control only with devices that
are slaves of your 1771-SDN Scanner Module. These slave devices
must be mapped in the scanner module’s scan list.

Use the Explicit Message Program Control feature to:

Transmit configuration data from your scanner module to its slave
devices on your DeviceNet network.