Using devicenet explicit messaging – Rockwell Automation 2100-GK61 DeviceNet to SCANport User Manual
Page 93
Publication 2100-UM001B-EN-P – January 2001
Chapter
6
Using DeviceNet Explicit
Messaging
Chapter Objectives
Chapter 6 provides information you need to monitor and configure
the SCANport device using explicit messaging on DeviceNet. In this
chapter, you will read about the following:
•
Required equipment.
•
Message translations.
•
Messaging guidelines for the 1771-SDN scanner.
•
Messaging guidelines for the 1747-SDN scanner.
•
Example messages.
•
Using messages to control SCANport products.
•
Writing to register objects.
Refer to Appendix C, DeviceNet Objects, for information on object
data support.
Required Equipment
Before using messaging, your PC must be:
•
Running Logix5 and RSLinx if you are using a PLC. Refer to
http://www.software.rockwell.com for more information on these
products.
-OR-
Running RSLogix500 and RSLinx if you are using an SLC. Refer
to http://www.software.rockwell.com for more information on
these products.
•
Connected to and communicating with the DeviceNet network
using a 1784-PCD card, 1784-PCID, card or a 1770-KFIO
adapter.
Explicit Message Program
Control for PLC-5
Use the Explicit Message Program Control feature to configure
device parameters on your DeviceNet network via the ladder logic
program in the PLC-5 processor that is controlling these devices.
You can use Explicit Message Program Control only with devices that
are slaves of your 1771-SDN Scanner Module. These slave devices
must be mapped in the scanner module’s scan list.
Use the Explicit Message Program Control feature to:
•
Transmit configuration data from your scanner module to its slave
devices on your DeviceNet network.