beautypg.com

Rockwell Automation 2100-GK61 DeviceNet to SCANport User Manual

Page 138

background image

Publication 2100-UM001B-EN-P – January 2001

B-12

DeviceNet to SCANport Communication Module with Digital Inputs Parameters

1. In the Polled section, click on the box next to Polled. A “✔”

appears.

2. In the Rx field, enter the size for the I/O input. Enter 4 for each

datalink enabled and 6 if Com/Ref is enabled. For example, if
Cmd/Ref and all 4 datalinks are enabled, you would enter 22.

3. In the Tx field, enter the size of the I/O output. Enter 4 for each

datalink enabled and 4 if Com/Ref is enabled. For example, if
Cmd/Ref and all 4 datalinks are enabled, you would enter 20.

4. In the Poll Rate field, select the appropriate rate.

5. In the Change of State/Cyclic section, click the box next to

Change of State/Cyclic. A “✔” appears.

6. Click Cyclic.

7. In the Rx field, enter 6 for the size of the I/O input.

8. In the Send Rate field, enter the time for the message interval.

9. Click OK.

Using Peer-to-Peer
Communications

To have your adapter receive data from or transmit data to another
2100-GK61, 1203-GU6, or 1336-GM6 on the DeviceNet network,
you must configure it for peer-to-peer communications. Peer-to-peer
communications are best used in the following instances:

A PLC sends data to a drive. That drive re-transmits the data to
other drives on the network.

A drive is configured on a network. It sends data to other drives
on the network.

Important: After setting up peer-to-peer communications, you must
make sure the configuration that you set up works as you intend it to
work.

Step #5

Step #6

Step #1

Figure B.7
Edit Device I/O Parameters Dialog Box for Polling and Cyclic