DeviceNet Objects

C-9

Instance Attributes

Setting of an assembly attribute can only be accomplished through a
connection. This feature is to prevent accidental control of the
SCANport product.

Common Services

Attribute

ID

Access

Rule

Name

Data

Type

Description

1

Get

Bad Flag

BOOL

If set to 1, then attribute
4 may contain invalid,
bad or otherwise
corrupt data.
0 = good
1 = bad

2

Get

Direction

BOOL

Direction of data
transfer.
0 = Producer Register
1 = Consumer Register

3

Get

Size

UINT

Size of register data in
bits.

4

Condi-

tional

Data

ARRAY
of BITS

Data to be transferred.

The access rule of Set is optional if attribute 2, Direction = 1. If Direction = 0, the access
rule is Get.

Service

Code

Implemented for

Service Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single