beautypg.com

Rockwell Automation 2100-GK61 DeviceNet to SCANport User Manual

Page 192

background image

Publication 2100-DU021B-EN-P - January 2004

Ladder Logic Programming—Including Reading Inputs 5-7

Table 5.H PowerFlex 70 and PowerFlex 700 Drives Logic Control

Logic Bits

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Status

Description

X

Stop

0 = Not Stop
1 = Stop

X

Start

0 = Not Start
1 = Start

X

Jog

0 = Not Jog
1 = Jog

X

Clear Faults

0 = Not Clear Faults
1= Clear Faults

X

X

Direction

00 = No Command
01 = Forward
10 = Reverse Command
11 = Hold Direction Control

X

Local
Control

0 = Not Local Control
1 = Local Control

X

MOP
Increment

0 = Not Increment
1 = Increment

X

X

Accel Rate

00 = No Command
01 = Accel Rate 1 Command
10 = Accel Rate 2 Command
11 = Hold Decel Rate

X

X

Decel Rate

00 = No Command
01 = Decel Rate 1 Command
10 = Decel Rate 2 Command
11 = Hold Decel Rate

X

X

X

Reference
Select

000 = No Command
001 = Ref. 1 (Ref A Select)
010 = Ref. 2 (Ref B Select)
011 = Ref. 3 (Preset 3)
100 = Ref.4 (Preset 4)
101 = Ref.5 (Preset 5)
110 = Ref. 6 (Preset 6)
111 = Ref. 7 (Preset 7)

X

MOP
Decrement

0 = Not Decrement
1 = Decrement