Rockwell Automation 2100-GK61 DeviceNet to SCANport User Manual
Page 23
Publication 2100-UM001B-EN-P – January 2001
Installation
2-3
Class 1 Drop Cable is available in three spool sizes:
For more information on DeviceNet cables and cable systems, refer to
the DeviceNet Cable System Planning and Installation Manual,
Publication DN-6.7.2.
Input Wires
Choose a suitable wire to handle 230Vac, 115Vac, or 24Vdc voltage,
depending on installation. The input connector is capable of installing
12-24AWG wire.
Installing the DeviceNet to SCANport Communication
Module with Digital Inputs (2100-GK61)
The following instructions explain how to physically install your
DeviceNet to SCANport Communication Module with Digital Inputs.
1. Before installing the module, set the Digital Input selection
switch SW1 to the proper input voltage per the table below.
Cable Part Number
Spool Size
1485C-P1-B50
50m (164 ft.)
1485C-P1-B150
150m (492 ft.)
1485C-P1-B300
300m (984 ft.)
!
ATTENTION: Severe injury or death can result from
electrical shock, burn, or unintended actuation of controlled
equipment. Hazardous voltages may exist in the cabinet even
with the circuit breaker in the off position. Recommended
practice is to disconnect and lock out control equipment from
power sources and discharge stored energy in capacitors, if
present. If it is necessary to work in the vicinity of energized
equipment, the safety related work practices of NFPA 70E,
Electrical Safety Requirements for Employee Workplaces,
must be followed.
ATTENTION: DO NOT work alone on energized
equipment!
VIN
SW1
#1
#2
230Vac
OFF
OFF
115Vac
OFF
ON
24Vdc
ON
OFF