Installation

2-3

Class 1 Drop Cable is available in three spool sizes:

For more information on DeviceNet cables and cable systems, refer to
the DeviceNet Cable System Planning and Installation Manual,
Publication DN-6.7.2.

Input Wires

Choose a suitable wire to handle 230Vac, 115Vac, or 24Vdc voltage,
depending on installation. The input connector is capable of installing
12-24AWG wire.

Installing the DeviceNet to SCANport Communication
Module with Digital Inputs (2100-GK61)

The following instructions explain how to physically install your
DeviceNet to SCANport Communication Module with Digital Inputs.

1. Before installing the module, set the Digital Input selection

switch SW1 to the proper input voltage per the table below.

Cable Part Number

Spool Size

1485C-P1-B50

50m (164 ft.)

1485C-P1-B150

150m (492 ft.)

1485C-P1-B300

300m (984 ft.)

!

ATTENTION: Severe injury or death can result from
electrical shock, burn, or unintended actuation of controlled
equipment. Hazardous voltages may exist in the cabinet even
with the circuit breaker in the off position. Recommended
practice is to disconnect and lock out control equipment from
power sources and discharge stored energy in capacitors, if
present. If it is necessary to work in the vicinity of energized
equipment, the safety related work practices of NFPA 70E,
Electrical Safety Requirements for Employee Workplaces,
must be followed.

ATTENTION: DO NOT work alone on energized
equipment!

VIN

SW1

#1

#2

230Vac

OFF

OFF

115Vac

OFF

ON

24Vdc

ON

OFF