beautypg.com

Rockwell Automation 2100-GK61 DeviceNet to SCANport User Manual

Page 118

background image

Publication 2100-UM001B-EN-P – January 2001

6-26

Using DeviceNet Explicit Messaging

4. Select a message type of CIP Generic. The next information

(Object Type, Object ID, and Object Attribute) corresponds to
DeviceNet Class, Instance, and Attribute. Service code is the
same service code used in DeviceNet.

Note: Class, instance, and attribute information can be found in
Appendix B of the E3 Overload Relay User Manual. For example:

Overload Object - Class Code 0x2C

Instances Supported – 1

Attribute 112 (0x70) – Time to trip

Service Code Supported – 0x0E (Message type –
Get_Attribute_Single)

Note: Numbers that start as 0x are hexadecimal numbers. All other
numbers are decimal.

Figure 6.14